Leoch Containerized C&I
Energy Storage System
Leading the Global Energy Transition Through Storage
Renewable Utilities
Peak Shaving
Frequency Regulation
Ramp Rate Control
Backup Power
Microgrid
Efficient Management
_______
– Equipped with BMS, PCS, and EMS for 3S linkage monitoring, it offers real-time data collection and analysis, enabling digital intelligent operation and control.
Easy to Install
_______
– Featuring a highly integrated AC/DC compartment, making it easy to install, maintain, and access.
– Offering flexibility and a variety of methods for diverse applications.
Environmental Adaptability
_______
– Designed to withstand windy and sandy conditions with IP54-rated container and IP67-rated battery pack
– Engineered for industrial areas with C4 anti-corrosion design.
Premium Safety and Reliability
_______
– The liquid-cooled temperature control system offers real-time, balanced, and efficient operation.
– State-of-the-art fire mitigation & suppression system
– Designed to save energy, extend battery life, and enhance safety.
Leoch’s Energy Management System (EMS) is a state-of-the-art solution designed to optimize the performance and efficiency of energy storage systems. Tailored for your specific needs, Leoch’s EMS is your path to smart, insightful, cost-effective energy management.
Comprehensive Management
_____
– Gain Insights into sites, systems, and equipment
– Enable remote management and control
– Historical data and operating curves
– ldentify and analyze trends
Access Real-Time Visualizations
_____
– Hierarchical and graphical data
– Monitor rich metrics at a glance
– Streamline operations and maintenance
– Gain Insights into sites, systems, and equipment
– Enable remote management and control
– Historical data and operating curves
– ldentify and analyze trends
– Hierarchical and graphical data
– Monitor rich metrics at a glance
– Streamline operations and maintenance
– Frequency Regulation Renewables Firming
– Ramp Rate Control Demand Management
– Capacity Dispatch Intermittency Smoothing
– Load Management Microgrid
System Model | Epoch-S2580/5015-40L |
DC Side Parameters | |
Cell type | LFP314 |
Pack configuration | 1P104S |
Cluster configuration | 1P104S / 4 packs |
System configuration | 12*1P416S |
Normal voltage | 5015kWh |
Voltage range | 1040~1518.4Vdc |
Charge discharge rate | 0.5C |
AC Side Parameters | |
Rated power | 2580kVA |
AC voltage | 690Vac/586~759Vac |
Grid frequency | 50/60Hz±3Hz |
AC access method | 3P4W+PE |
Power factor | -1~1 |
Maximum THD | <3%(@rate power) |
System Parameters | |
Size (W*D*H) | 12192mm*2896mm*2438mm |
Weight | 43t |
IP level | IP54 |
Working altitude | No downgrading below 3000 meters |
Operating temperature | -20℃~55℃ |
Operating noise | ≤75dB(A) |
Cooling method | Intelligent liquid cooling |
Fire protection system | Cabin level aerosol + Water spray fire protection |
Communication protocol | CAN, Modbus TCP/IP |
Certificate | GB/T36276, GB/T34131, UL9540, UL1973, UL9540A |